QA

Quick Answer: How Many Ac Tons Per Square Feet

Simple answer: You need 0.0016 tons of AC per square foot. In general, for every 600 sq ft, you need 1 ton of AC. This is a general estimate.

How many square feet will a 2 ton AC cool?

Air Conditioning Square Footage Range by Climate Zone ZONE 1 ZONE 4 1.5 Tons 600 – 900 sf 700 – 1050 sf 2 Tons 901-1200 sf 1051 – 1350 sf 2.5 Tons 1201 – 1500 sf 1351 – 1600 sf 3 Tons 1501 – 1800 sf 1601 – 2000 sf.

How many tons AC do I need?

To estimate your AC tonnage needs, multiply the number of square feet you’re cooling times 25. This equals the total number of BTUs you need to adequately cool your space. Next, divide that number by 12,000 to determine the tonnage capability you need in your new air conditioning unit.

What size air conditioner do I need for a 3000 square foot house?

The recommended capacity for a home that is 1,201 to 1,500 square feet is 2.5 tons. For a home 1,501 to 1,800, the recommended capacity is 3 tons. For a 2,000 square-foot home, the best AC capacity is 3.5 tons. Since larger homes are costlier to cool, you’ll need a 5-ton unit to cool a 3,000 square-foot home.

How many square feet will a 4 ton AC cool?

ZONE 1 ZONE 4 3 Tons 1501 – 1800 sf 1601 – 2000 sf 3.5 Tons 1801 – 2100 sf 2001 – 2250 sf 4 Tons 2101 – 2400 sf 2251 – 2700 sf 5 Tons 2401 – 3000 sf 2751 – 3300 sf.

How many sq ft will a 2.5 ton AC cool?

For example, a 30,000 BTU, 2.5-ton air conditioner is made to effectively cool a home between 1,200 and 1,500 square feet. A slightly larger 3,600, 3-ton unit, is designed for homes that are 1,500 to 1,800 square feet.

What size AC do I need for 2000 square feet?

Step 5: Match your square footage to an HVAC size chart Home Sq Footage Air Conditioner Size (tons) 600 – 1,000 square feet 1.5 tons 1,000 – 1,500 square feet 2 tons 1,500 – 2,000 square feet 3 tons 2,000 – 2,500 square feet 4 tons.

What size air conditioner do I need for a 2400 square foot home?

The answer to the question, “what size AC unit for 2400 square feet?”, would be, is 60,000 BTUs or 5 Tons. It’s possible to fall between unit sizes, so if that’s the case with you, then you should choose the next higher size. That way, you can be sure that the AC unit can still cool a given area sufficiently.

How many tons is 1200 square feet?

2 Tons Area (Square Feet): BTU Tonnage 600 sq ft 12,000 BTU 1 Ton 900 sq ft 18,000 BTU 1.5 Tons 1,200 sq ft 24,000 BTU 2 Tons 1,500 sq ft 30,000 BTU 2.5 Tons.

What happens if you oversize an air conditioner?

An oversized HVAC unit can make your home’s inside temperature uncomfortable. An HVAC system with excess capacity can heat or cool your home faster, but that speed often results in a couple of other issues. As a result, you could end up with a number of hot or cold spots throughout your home.

How much should a 3 ton AC unit cost installed?

AC Installation Costs by Tons Central Air Conditioner Size AC Unit BTU AC Unit Only 2.5 Tons 30000 BTU $2,895 3 Tons 36000 BTU $2,920 3.5 Tons 42000 BTU $3,550 4 Tons 48000 BTU $3,650.

Is a 3 ton air conditioner enough?

Pro Tip: as a rule of thumb, the maximum AC unit size you need to install should not be more than 15% more than the BTU’s you need to cool your house. This means that if your house requires a 24,000 BTU unit (2 tons), you should not install one that is larger than 30,000 BTU’s (3 tons) to maintain energy efficiency.

Is a 2-ton AC big enough?

For those of you that don’t understand the way AC systems work, a 2-ton unit typically provides cooling for about 900-1,400 square feet of space – give or take.

What size AC do I need for 1800 sq ft house?

Here’s some math: You need around 20 BTUs per square foot, which is equivalent to 0.0016 tons. For example, a 600-square-foot space requires a 12,000 BTU or 1-ton unit. By those calculations, an average 1,800-square-foot house would need a 3-ton central air conditioning unit.

Which AC is suitable for 12×12 room?

According to Energy Star, a 12×12′ or 144 sqft room requires 5,000 BTU of cooling capacity when occupied by two persons. If the room is heavily shaded, it only requires 4,500 BTU. If the room is very sunny, it requires 5,500 BTU. For each additional person, you need to add 600 BTU.

How much does a 5 ton air conditioning unit cost?

On average, you can expect a 5 ton AC unit to cost about $3,700, while a 3 ton AC unit can cost as little as $2,900. It’s important to remember that the price you pay for HVAC system components also depends on where you shop. A 5 ton AC unit that costs $3,700 from one shop may only cost $3,200 from another.

Can you replace a 2 ton AC unit with a 3 ton?

Simple answer: yes. But that really depends on the size of you house and its condition. If the 2 ton unit is working as designed but seems to run continuously without satisfying the thermostat setting, then it might be undersized and replacing it with a 3 ton unit might be the answer.

How much AC do I need for 400 square feet?

STEP 1: Determine how many BTUs of heating and tons of AC you need House Square Footage BTUs Needed 250 – 300 7,000 300 – 350 8,000 350 – 400 9,000 400 – 450 10,000.

Is 2.5 ton AC big enough?

According to this common but somewhat inaccurate method, you need 1 ton of air cooling capacity for every so many square feet of living space. While there’s some dispute over the exact amount, an often-used amount is 600 square feet. A 2.5-ton unit, then, theoretically would fit a 1,500-square-foot home.