QA

Quick Answer: What Does The Voltage Rating On A Fuse Mean

The voltage rating is the maximum voltage that the fuse can safely operate at when an overcurrent situation happens. The voltage rating on the fuse can be higher than the voltage present on the circuit, but not the other way around. If a 250 VAC fuse is used on a device that uses 120 VAC, there should be no problem.

Does the voltage rating on a fuse matter?

The voltage rating of a fuse must be at least equal to or greater than the circuit voltage. It can be higher but never lower. If a fuse is used with a voltage rating lower than the circuit voltage, arc suppression will be impaired and, under some overcurrent conditions, the fuse may not clear the overcurrent safely.

Can I use a 250V fuse instead of 125V?

For example, a 125V fuse can be replaced with a 250V fuse of equal amplitude while the voltage of the application is 250V or lower, but a a 250V fuse can’t be replaced with a 125V fuse of equal amplitude if the voltage of the application exceeds 125V.

What happens if you use a higher voltage fuse?

If you use a higher voltage rated fuse the clearing time will be increased above the fuses specification. In the worst case a longer clearing time could result in damage to the power source and wiring, the device being protected, or both.

What is the difference between 125V and 250V fuse?

Once the fusible wire inside the fuse burns open, a 125V fuse is more prone to arc across the blown leads inside the fuse. The 250V fuse can sustain a higher voltage before it arcs over. So yes, you can use a 250V fuse in place of a 125V fuse as long as the current rating is the same.

Do fuses care about voltage?

Is the voltage rating important? Yes, very important! The voltage rating of the selected fuse must be greater than or equal to the circuit voltage. Since fuses have such low resistance, the voltage rating becomes critical only when the fuse is trying to open.

How do I choose the right rating of a fuse?

In order to select the right amperage of the fuse, you first need to know the full-load steady-state current of the circuit at an ambient temperature of 25º C (68º F). Once the current value is determined, then a fuse rating should be selected as to be 135% of this value (taken to the next standard value).

How many amps is a 125V fuse?

Type TL Time Delay Glass Plug Fuse 125-Volt 20 Amp (Pack-4).

What is the difference between 120v and 125V?

2 Answers. 120v and 125v outlets are nominally identical. You must have something miswired, or you have a rare faulty unit. Be sure you have power connected to the LINE side.

What does 125V 250V mean?

When looking at our product descriptions, you’ll often notice a “125/250 Volts” for our products with 4 prongs. If your application for our adapter only requires 125 volts, then only one hot wire will be used. If it requires 250 volts, then both hot wires will be used.

Can you replace a 15 amp fuse with a 30 amp fuse?

In fact, a 20 or 30 Amp fuse or breaker on a 15 Amp circuit becomes an armed fuse of a ticking fire bomb! You replace it with another 15 Amp one. It blows again and again. Now you replace it with a 20 Amp fuse.

What happens if you put a 15 amp fuse in a 10 amp slot?

If you were to say replace a 15 amp fuse on your power outlet with a 10 amp it would work perfectly fine to charge your phone but will probably blow if you tried to run an air compressor.

What happens if I put a 20 amp fuse in a 15 amp slot?

The 15 amp slot is designed for handling current upto 15 amps so if you put a 20 amp fuse in a 15 amp slot and draw a current greater than 15 amps there will be heating and other issues like molten insulation you can put a 20 amp fuse only if u know that u are not going to draw more than 15 amps.

Does voltage matter on a glass fuse?

Originally Answered: Does voltage matter on a fuse? Yes it does. A fuse needs to ‘break’ the circuit, and if the ‘gap’ is small enough a high voltage will ‘arc over’ -the plasma thus formed is a good conductor and will allow the current to keep flowing.

Can I use a 125V cord on a 250V?

It is possible to use a power cord that is rated higher than the maximum you need. The original cord had a rating of 10A, 125V. The one you found is rated at 10A and will give you twice the power as it will actually encounter.

Can I use a 32 volt fuse in place of a 250 volt fuse?

Question: Will this 250v 4 amp fuse work to replace a 4amp 32v fuse (in an old amplifier/receiver)? 250V is the max current the fuse can take, it is fine as long as that rating is at or above the current being passed through the fuse, in this case 32V. Howver for amps, you should use slow blow.

Do fuses protect against high voltage?

If you use a fuse that’s too big, it won’t protect your appliance from excessive currents and you may put yourself, your home, and your life at risk.Which fuse should you use? Fuse rating Power rating (for 240 volt supply) 13 amp Over 1200 watts.

Does fuse have voltage drop?

The voltage drop across a fuse is generally low and depends upon the fuse rating. A lower current rated fuse has a higher resistance. This resistance is usually stated in the data sheet for the particular fuse you are using.

What is the minimum voltage rating of branch circuit fuses?

NEC 240.60(C) states that the minimum interrupting rating of branch-circuit cartridge fuses is 10,000 A.

What fuse do I need for 12v?

if the device load is known in watts, divide the wattage by voltage-(i.e 100watts divided by 12v = 8.3 amps) -use 10 amp fuse.