QA

What Size Air Conditioner For 1500 Square Feet

Therefore, if your home is 1,500 square feet, your air conditioning unit should be 3.5 to four tons.

What size AC unit do I need for a 1600 sq ft house?

ZONE 1 ZONE 3 1.5 Tons 600 – 900 sf 600 – 1000 sf 2 Tons 901 – 1200 sf 1001 – 1300 sf 2.5 Tons 1201 – 1500 sf 1301 – 1600 sf 3 Tons 1501 – 1800 sf 1601 – 1900 sf.

How many square feet does a 3-ton AC unit cover?

3-ton is equal to 36,000 BTU. If you apply the 20 BTU per sq ft rule of thumb, you can see that a 3-ton air conditioner cools about 1,800 square feet spaces.

How many BTUs do I need to cool 1500 square feet?

Size and Ceiling Height Area To Be Cooled (square feet) Capacity Needed (BTUs per hour) 1,200 to 1,400 23,000 1,400 to 1,500 24,000 1,500 to 2,000 30,000 2,000 to 2,500 34,000.

How many square feet will a 2.5 ton AC cool?

For example, a 30,000 BTU, 2.5-ton air conditioner is made to effectively cool a home between 1,200 and 1,500 square feet. A slightly larger 3,600, 3-ton unit, is designed for homes that are 1,500 to 1,800 square feet.

How much should a 3 ton AC unit cost installed?

AC Installation Costs by Tons Central Air Conditioner Size AC Unit BTU AC Unit Only 2.5 Tons 30000 BTU $2,895 3 Tons 36000 BTU $2,920 3.5 Tons 42000 BTU $3,550 4 Tons 48000 BTU $3,650.

What size AC unit do I need for a 1800 sq ft house?

Here’s some math: You need around 20 BTUs per square foot, which is equivalent to 0.0016 tons. For example, a 600-square-foot space requires a 12,000 BTU or 1-ton unit. By those calculations, an average 1,800-square-foot house would need a 3-ton central air conditioning unit.

How many tons do I need for a 1500 square-foot house?

2.5 Tons Square Footage BTUs per hour AC Unit Tonnage 1,200 to 1,400 23,000 2 Tons 1,400 to 1,500 24,000 2 Tons 1,500 to 2,000 30,000 2.5 Tons 2,000 to 2,500 34,000 3 Ton.

Is the a big difference between a 2.5 ton and 3 ton AC?

The general guideline is a 2.5 ton unit for a home that’s 1,500 to 2,000 square feet. A 3 ton unit is ideal for a home that’s 2,000 to 2,500 square feet.

Which AC is suitable for 12×12 room?

According to Energy Star, a 12×12′ or 144 sqft room requires 5,000 BTU of cooling capacity when occupied by two persons. If the room is heavily shaded, it only requires 4,500 BTU. If the room is very sunny, it requires 5,500 BTU. For each additional person, you need to add 600 BTU.

What size AC do I need calculator?

How do I Calculate What Size Air Conditioner I Need? Room Size for Air Conditioner Air Con Capacity 10m2 to 25m2 2.5 kW 25m2 to 35m2 3.5 kW 35m2 to 60m2 5-6 kW 60m2 to 85m2 7-8.5 kW.

How many square feet will a 5000 BTU air conditioner cool?

The size of your space determines how much cooling capacity you need. Budget air conditioners range from 5,000 BTU, which can handle about 150 square feet, to 12,000 BTU, enough to cover about 550 square feet.

What size AC do I need for 1200 sq ft?

STEP 1: Determine how many BTUs of heating and tons of AC you need House Square Footage BTUs Needed 500 – 700 14,000 700 – 1,000 18,000 1,000 – 1,200 21,000 1,200 – 1,400 23,000.

What size AC unit do I need for a 1300 sq ft house?

When looking for the quick answer to how much air-conditioning power you’ll need to adequately cool a 1,300-square-foot space, the answer is 23,000 BTUs per hour of air conditioning power. This is the base capacity needed for a 1,200- to 1,400-square-foot house.

Can you replace a 2 ton AC unit with a 3 ton?

Simple answer: yes. But that really depends on the size of you house and its condition. If the 2 ton unit is working as designed but seems to run continuously without satisfying the thermostat setting, then it might be undersized and replacing it with a 3 ton unit might be the answer.

Is a 3 ton air conditioner enough?

Pro Tip: as a rule of thumb, the maximum AC unit size you need to install should not be more than 15% more than the BTU’s you need to cool your house. This means that if your house requires a 24,000 BTU unit (2 tons), you should not install one that is larger than 30,000 BTU’s (3 tons) to maintain energy efficiency.

How much does an air conditioner cost for a 1500 sq ft home?

Cost of central air for 800 – 3,000 sq ft house House Size (sq ft) Central Air Equipment Cost Central Air Installed Cost 1,100 sq ft $2,400 – $6,000 $3,550 – $8,600 1,200 sq ft $2,950 – $6,000 $4,300 – $8,600 1,500 sq ft $3,300 – $7,150 $4,650 – $9,900 1,600 sq ft $3,300 – $7,700 $4,650 – $10,650.

What SEER rating should I buy?

There’s no magic SEER number. Anything over 13 is great. Because if you have an old 8 SEER system and replace it with a 16 SEER unit, you could significantly reduce the cost of cooling your home. Don’t forget to look at tax credits and manufacturer’s rebates that can bring the down the cost of a high SEER system.

Is it cheaper to replace furnace and AC together?

Adding a furnace during your air conditioner replacement will cost a lot less, around $1,000 to $3,000. The only time it really makes sense to wait to replace your furnace is if it is less than 10 years old. This way, the furnace will most likely last until the next time your air conditioner needs to be replaced.